Features :
- Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W
- Voltage & Current are the True RMS value.
- True Power ( KW、MW、GW ) measurement.
- Apparent Power ( KVA、MVA、GVA ) measurement.
- Reactive Power ( KVAR MVAR、GVAR) measurement.
- Watt-Hour ( WH、SH、QH、PFH ).
- Power Factor( PF )、Phase Angle( Φ ).
- Voltage measurement range : 10 to 600 ACV
- Current measurement range: 0.2A to 1200 ACA.
- Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
- ACV input impedance is 10 Mega ohms.
- Safety Standard : IEC 1010, CAT III 600V
- Built-in clock and Calendar, real time data record with SD memory card , sampling time set from 2 to 7200 seconds. Just slot in the SD card into the computer, it can down load the all the measured value with the time information ( year/month/data/hour/mimute/second ) to the Excel directly, then user can make the further data analysis by themselves.
- Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe, AC to DC 9V adapter, 2 G SD memory card and Carrying bag.
- Computer data output, can cooperate with USB Cable /USB-01 RS232 cable/UPCB-02 and Data Acquisition software, SW-U811-WIN.
Specifications :
- Circuit: Custom one-chip of microprocessor LSI circuit
- Display:
- LCD Size : 81.4 X 61 mm ( 3.2 X 2.4 inch )
- Dot Matrix LCD (320 X 240 pixels ) with back light.
- Measurement:
- ACV
- ACA
- AC WATT ( True Power )
- AC WATT( Apparent Power )
- AC WATT( Reactive Power )
- Power factor
- Phase angle
- Frequency
- Wire connections: 1P/2W, 1P/3W, 3P/3W, 3P/4W.
- Voltage ranges: 10 ACV to 600 ACV, auto range.
- Current ranges: 0.2 ACA to 1200 ACA, auto range/manual range.
- Safety standard: IEC1010 CAT III 600 V.
- ACV input impedance: 10 Mega ohms.
- Range select:
- ACV: Auto range.
- ACA: Auto range & manual range.
- Clamp frequency response: 40 Hz to 1 KHz.
- Spec. tested frequency: 45 to 65 Hz.
- Over load protection:
- ACV: 720 ACV rms
- ACA: 1300 ACA with clamp probe CP-1200
- Over Indicator: Show ” OL “.
- Under Indicator: Show ” UR “.
- Data Hold: Freeze the display reading.
- Data Record: SD Card Record
- Sampling Time: Approx. 1 second.
- Power ON/OFF: Manual OFF by push button.
- Real time data logger:
- Real time data logger, saved the data into SD memory card and down load the all the measured value with the time information ( year/month/data/hour/mimute/second ) down load to the Excel.
- Integration time for data logger : 2 seconds to 7200 seconds, the during of setting step are 2 seconds.
- Data Output USB/RS232: RS232 computer serial interface :
- Connect the optional USB cable USB-01 will get the USB plug.
- Connect the optional RS232 cable UPCB-02 will get the RS232 plug.
- Operating Temperature: 0 to 50℃ ( 0 to 122℉ ).
- Operating Humidity: Less than 80% R.H..
- Power Supply:
- DC 1.5V, AA ( UM-3 ) Battery X 8 PCs (Alkaline or heavy duty battery).
- AC to DC 9V power adapter.
- Power Consumption:
- Meter : 300 DCmA.
- Clamp : 20 DCmA
- Clamp max. conductor Size: 86 mm ( 3.4 inch ) Dia.
- Weight:
- Meter: 1049g ( includes batteries )
- Clamp : 522g
- Dimension:
- Meter : 225 X 125 X 64 mm ( 8.86 X 4.92 X 2.52 inch )
- Clamp : 210 X 64 X 33mm ( 8.3 X 2.5 X 1.3 inch )
- Clamp Jaw : 50 mm (2.0 inch)- outside
Accessories Included :
- Instruction manual…………………..1 PC
- Test Leads (TL88-4AT)…………….. 1 Set (4 PCs)
- Alligator clips (TL88-4AC)…………..1 Set (4 PCs)
- Clamp Probe ( CP-1200 )………….. 3 PCs
- AC to DC 9V adapter…………………1 PC
- SD card ( 2 G )………………………. 1 PC
- Carrying bag…………………………..1 PC
Pilihan produk luas
Diskon up to 30%
Full garansi satu tahun
Pengiriman gratis