Features:

  • Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W
  • 3 current probes max 1200A AC (CP-1201) are included
  • Current range : 0.2 to 1200 ACA –>CP-1201
  • Current probe input signal/ranges with selection:
    Input signal (ACV): 200 mV/300 mV/500 mV/1 V/2 V/3 V
  • Meter can cooperate with other universal current probes
  • Voltage & Current are the True RMS value
  • True Power (KW, MW, GW)
  • Apparent Power (KVA, MVA, GVA)
  • Reactive Power (KVAR, MVAR, GVAR)
  • Watt-Hour (WH, SH, QH, PFH)
  • Power Factor (PF), Phase Angle (Degree)
  • Voltage range : 10 to 600 ACV
  • Programmable CT ratio (1 to 600) and PT ratio (1 to 1000)
  • ACV input impedance is 10 Mega ohms
  • Safety Standard : IEC 1010, CAT III 600V

Accessories Included :

  • 4 PCs Test Leads
  • 4 PCs Alligator clips
  • 3 PCs Clamp Probe 1200A (CP-1201)
  • AC to DC 9V adapter
  • 4 GB SD card
  • Carrying bag
  • Instruction Manual
  • Certificate Calibration

  • Specifications Lutron DW-6093 3 Phase Power Analyzer
    • Circuit: Custom one-chip of microprocessor LSI circuit
    • Display:
      º LCD Size : 81.4 X 61 mm ( 3.2 X 2.4 inch )
      º Dot Matrix LCD (320 X 240 pixels ) with back light.
    • Measurement:
      º ACV
      º ACA
      º AC WATT ( True Power ), AC WATT( Apparent Power ), AC WATT( Reactive Power )
      º Power factor
      º Phase angle
      º Frequency
    • Wire connections: 1P/2W, 1P/3W, 3P/3W, 3P/4W
    • Voltage ranges: 10 ACV to 600 ACV, auto range.
    • Current probe input signal and range:
      º Current probe input signal volage ( ACV ) : 200mV/300mV/500mV/1V/2V/3V
      º Current probe input current range ( ACA ) : 20 A/200A/2000A (1200 A)/30A/300A/3000A
      º Meter can cooperate the universal current probe.
    • Safety standard: IEC1010 CAT III 600 V.
    • ACV input impedance: 10 Mega ohms.
    • Range select:
      º ACV: Auto range.
      º ACA: Manual range.
    • Clamp frequency response: 40 Hz to 1 KHz.
    • Spec. tested frequency: 45 to 65 Hz.
    • Over load protection:
      º ACV: 720 ACV rms
      º ACA: 1300 ACA with clamp probe
    • Over Indicator:
      º LCD display show ” OL “.
      º The data save into the SD card will show ” 9999 ” or ” 999 ” ( overleap the decimal point )
    • Under Indicator:
      º LCD display show ” UR “.
      º The data save into the SD card will show ” 9999 ” or ” 999 ” ( overleap the decimal point )
    • Data Hold: Freeze the display reading.
    • Data Record: SD Card Record.
    • Sampling Time: Approx. 1 second.
    • Power ON/OFF: Manual OFF by push button.
    • Real time data logger:
      º Real time data logger, saved the data into SD memory card and down load the all the measured value with the time information ( year/month/data/hour/minute/second ) down load to the Excel
      º Sampling time for data logger : 2 seconds to 7200 seconds, the during of setting step are 2 seconds.
    • Data Output USB/RS232: RS232 computer serial interface :
      º Connect the optional USB cable USB-01 will get the USB plug.
      º Connect the optional RS232 cable UPCB-02 will get the RS232 plug.
    • Operating Temperature: 0 to 50℃ ( 32 to 122℉ ).
    • Operating Humidity: Less than 80% R.H..
    • Power Supply:
      º DC 1.5V, AA ( UM-3 ) Battery X 8 PCs (Alkaline or heavy-duty battery).
      º AC to DC 9V power adapter.
    • Power Consumption:
      º Meter : 300 DCmA.
      º Clamp : 34 DCmA.
    • Clamp max conductor Size: 50 mm ( 2.0 inch ) Dia.
    • Weight:
      º Meter : 948g ( includes batteries )
      º Clamp ( includded cable ) : 467g
    • Dimension:
      º Meter : 225 X 125 X 64 mm ( 8.86 X 4.92 X 2.52 inch )
      º Clamp : 210 X 64 X 33mm ( 8.3 X 2.5 X 1.3 inch )
      º Clamp Jaw : 86 mm (3.4 inch)- outside